3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 213 GPM. Correct By: 15-Jun-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 07-June-2022
Comments |
---|
Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. The Certificate of Compliance is not available for the main drain cover. Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed 6/21/2019. The covers have a 7 year life span and must be replaced before 6/21/26. The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions. |