3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps. Flow meter in pump room was reading "0". Could not determine flow rate for outdoor pool.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. Depth markers to include "no diving" warning signs are not visible on the pool deck.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
3701-31-04 (E)(3)(a) / "WARNING, NO LIFEGUARD", sign posted
Repeat The unguarded pool was in use without the "WARNING, NO LIFEGUARD" sign posted.
Post the WARNING, NO LIFEGUARD sign in a conspicuos location at all times the pool is available for use.
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
Repeat The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 20-July-2021