[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The main drain covers has exceeded their life span.
REPLACE THE MAIN DRAIN COVERS OR PROVIDE DOCUMENTATION AS TO THE DATE OF INSTALLATION OF THE DRAIN COVERS, THE NAME OF THE INSTALLER, AND THE CERTIFICATE OF INSTALLATION. POST THE COC IN PUMP ROOM WHEN INSTALLED. Correct By: 09-Jul-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The weirs are missing in the skimmers
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIRS IN THE SKIMMERS. Correct By: 09-Jul-2019
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present. The hose bib in the pump room is not backflow protected.
Remove all cross connection hazards from the pool area. INSTALL AN ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB IN THE PUMP ROOM. Correct By: 09-Jul-2019
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. FLOW RATE MUST BE 175 GPM AT THE MINIMUM
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The fence has large gaps between the ground and the bottom of the fence. The gate does not self-close and latch.
ELIMINATE GAPS IN THE FENCE OF 4 INCHES OR GREATER BETWEEN THE BOTTOM OF THE FENCE AND GROUND. REPAIR THE GATE SO THAT IT SELF-CLOSES AND LATCHES. Correct By: 09-Jul-2019
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
Repeat 12 ft. non-telescopic reach pole with Shepherd's crook was not provided at the guarded pool.
Provide the non-telescopic reach pole at the pool at all times. KEEP SHEPHERD'S CROOK ATTACHED TO THE REACH POLE. Correct By: 09-Jul-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 09-July-2019

Comments
Please post main drain certificate of compliance in the pump room