3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
-Observed that alkalinity is not being recorded weekly.
-Test total alkalinity at least once per week.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
-Observed weir door missing.
-Replace missing weir door.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and lockable.
-Observed interior door to pool does not completely latch and close on its own.
-Repair gates or doors in order to be self-closing and lockable.
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
-Observed spray bottle with no label.
-Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
-Observed pH was below the acceptable range at <6.8
-Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
-Observed the alkalinity was below 60 ppm at 30ppm.
-Raise the total alkalinity to at least 60 ppm.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly.
- Observed the ACC unit not being recorded as tested monthly.
-Provide records indicating that the unit is being tested monthly.
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly.
-Observed expired reagents
-Obtain fresh reagents and store them properly.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 24-January-2024
Comments |
---|
-Observed the tested pH value of pool water did not match the pH value recorded on the ACC. Strongly recommend promptly having the ACC serviced or calibrated. -Ensure the water chemistry is being tested at the required frequencies. Compare the measured values to the ACC to ensure they match. -The Certificate of Compliance for the main drain covers is available in the equipment room. -Discussed the requirements for documenting accidents. -Due to the number of violations and two critical violations, a re-inspection will be conducted in approximately 1 week. |