3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical The chemical/pump room was 107 degrees which is a higher temperature than chemicals should be stored at.
REDUCE THE TEMPERATURE OF THE CHEMICAL/PUMP ROOM AND MAINTAIN TEMPERATURE BELOW 95 DEGREES. Correct By: 17-Aug-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 09-August-2019
Comments |
---|
When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm |