3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Less than the required 2 ppm free chlorine was in the spa (.6 ppm)
This violation is a critical operational item and poses an imminent health hazard.
THE SPA MUST CLOSE UNTIL THE FREE CHLORINE LEVEL IS 2 PPM OR MORE AND CAN BE MAINTAINED.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO BETWEEN 50 AND 63 GPM
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 20-August-2019
Comments |
---|
THE SKIMMER HAS AN EQUALIZER OUTLET WHICH IS A SUCTION HAZARD AND MUST BE PLUGGED AND COVERED WITH A VGB COMPLIANT COVER A PUMP CURVE FOR THE SPA JET PUMP IS NEEDED TO DETERMINE THE FLOW RATE. I'LL SEE IF I CAN FIND ONE FOR YOU |