3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention devices were not maintained to function properly. There are 2 hose bibs in the filter room that are not backflow protected.
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
INSTALL ASSE 1011 BACKFLOW PREVENTERS ON THE TWO HOSE BIBS IN TH FILTER ROOM. Correct By: 09-Jul-2017
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge. Only a air break now exists.
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP FOR THE FILTER BACKWASH LINE. Correct By: 09-Jul-2017
3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Throttle valve was not properly maintained/adjusted. The throttle valve was not tagged with the max and min flow.
TAG THE THROTTLE VALVE WITH THE MAXIMUM ALLOWABLE FLOW AND THE MINIMUM REQUIRED FLOW OR MARK THE PIPE BY THE FLOW METER WITH THE MAX AND MIN FLOW. MAXIMUM ALLOWABLE FLOW IS TO BE DETERMINED. THE MINIMUM REQUIRED FLOW IS 343 GPM. Correct By: 09-Aug-2017
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. Depth markings and "No diving" markings are more than 25 ft apart on the deck.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
PLACE ADDITIONAL DEPTH MARKINGS AND "NO DIVING" MARKINGS WHERE THEY ARE MORE THAN 25 FT APART. Correct By: 09-Aug-2017
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the pool.
Provide a proper floatation device at all times.
MAKE AVAILABLE AND VISIBLE A RING BUOY WITH A 30-60 FT ROPE. Correct By: 16-Jun-2017
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
The location of the emergency phone was not posted.
POST A SIGN THAT CAN BE READ FROM THE POOL DECK THAT STATES THE LOCATION OF THE EMERGENCY. Correct By: 16-Jun-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 09-June-2017
Comments |
---|
THE MAXIMUM ALLOWABLE FLOW FOR THE FILTERS AS MARKED ON THE DATA PLATE IS 410 GPM. THIS INFORMATION WILL BE VERIFIED WITH A CALL TO THE MANUFACTURER. THE FLOW METER IS NOT PROPERLY LOCATED. THE FLOW METER IS 17 INCHES UPSTREAM FROM THE 90 DEGREE ELBOW IN THE 6 INCH PIPE. THE BACKFLOW PREVENTER ON THE INCOMING CITY WATER DOES NOT APPEAR TO BE BACKFLOW PROTECTED. THE ASSE 1015 LOCATION IS IN QUESTION. THE TESTING OF THE UNIT ALSO DOES NOT APPEAR TO BE CURRENT. |