[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. CONTACT ODH TO GAIN APPROVAL FOR THE REPLACEMENT OF THE CIRCULATION PUMP.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required flow meter for the jet pump was not maintained or were not functional while the spa is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR THE FLOW METER FOR THE JET PUMP. Correct By: 23-Feb-2024


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 15-February-2024

Comments
THE TEMPERATURE OF THE SPA MUST NOT BE MORE THAN 104 DEGREE. ADJUST THE TEMPERATURE DOWN A LITTLE.

The Certificate of Compliance for the main drain covers is available in the equipment room. Our records show that the main drain suction outlet covers (AquaStar WAV12) were installed on 11-1-23. The covers have a 5 year life span and must be replaced before 11-1-28.