[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not installed. One of the equalizer outlets not covered.
Do not operate the pool when the outlet covers are not installed. EITHER PLUG THE EQUALIZER OUTLET OR INSTALL A VGB APPROVED OUTLET COVER. Correct By: 09-Jul-2021
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results. TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH FUNCTION MONTHLY AND RECORD IT ON THE WEEKLY LOG SHEETS. Correct By: 09-Jul-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The flow rate exceeds the max filter flow rating.
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE THE FLOW RATE TO LESS THAN 196 GPM TO PROTECT THE FILTER. Correct By: 09-Jul-2021
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage areas were not secured.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas. KEEP EQUIPMENT ROOM LOCKED. Correct By: 06-Jul-2021
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Corrected During Inspection Chemical containers were not stored properly. Degreeser and pH CYA were stored on top of the cal hypo.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure. DO NOT STORE DIFFERENT CHEMICALS ON TOP ON EACH OTHER. MOVE DEGREESER AND pH UP OFF OF THE CAL HYPO. Correct By: 06-Jul-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 06-July-2021

Comments
Corrections made since the last inspection dated 6-2-21
-weirs are in the skimmers
-backflow preventer is on the hose bib in the equipment room
-depth markings are acceptable
-pH is in the acceptable range

THE EMERGENCY PHONE IS LOOSE. I HAD TO GIGGLE IT TO GET IT TO WORK.