[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The weirs are missing in the skimmer boxes.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIRS IN THE SKIMMER BOXES. Correct By: 30-Jun-2018
3701-31-04 (B)(6)(j) / All SVRS devices are maintained/ functional and tested
Critical The SVRS was not tested and recorded.
TEST AND RECORD THE SVRS AT LEAST MONTHLY. Correct By: 20-Jun-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. INCREASE pH TO AT LEAST 7.2. Correct By: 20-Jun-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve on the ACC was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. TEST AND RECORD THE ACC FLOW SWITCH FUNCTION MONTHLY. Correct By: 20-Jun-2018


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 18-June-2018