3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THIS IS A CRITICAL OPERATION ITEM AND POSES AN IMMINENT HEALTH HAZARD. THE OPERATOR WAS INSTRUCTED TO TREAT THE POOL AND ENSURING THE FREE CHLORINE LEVEL IS AT LEAST 1 PPM BEFORE ALLOWING SWIMMERS INTO THE POOL. Correct By: 15-Jun-2023
3701-31-04 (B)(6)(cc)(ii) / Starting blocks and diving platforms shall not be accessible to patrons.
Starting blocks/diving platforms were accessible to patrons
Prevent the use of starting blocks/diving platforms by patrons.
BLOCK ACCESS TO THE STARTING BLOCKS UNTIL POOL IS CLOSED TO THE PUBLIC. Correct By: 15-Jun-2023
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gate was blocked open..
KEEP THE GATE CLOSED. Correct By: 15-Jun-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 15-June-2023
Comments |
---|
Keep documentation of the ASSE 1013 backflow preventer’s annual inspection available at the pool facility for review by the health department. The operator was observed performing onsite chemical tests appropriately Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed 5/1/2016. The covers have a 7 year life span and must be replaced before 5/1/2023. This drain cover has a maximum flow rating of 356 gpm. When replacing the covers, ensure that the new covers' flow rating will not be exceeded. 408 gpm The minimum required flow rate for a pool of this size is 408 gpm. The existing pump does not produce the required flow rate. |