3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records. Daily records have not keep kept for more than 3 months except for one day a week when the contracted pool company checks water.
All facility records must be maintained and available for review upon request.
KEEP DAILY OPERATIONAL RECORDS. POOL SHOULD NOT OPERATE IF RECORDS ARE NOT KEPT DAILY.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 57 GPM. Correct By: 08-Mar-2019
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Deck surfaces had standing water or other hazards. Mold is growing on the walls and floor where water condenses alone the outside walls.
Repair areas of the deck where standing water is occurring.
CLEAN AND DISINFECT THE AREA WHERE MOLD IS GROWING. Correct By: 08-Mar-2019
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. The 5 ft depth marker is missing.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
REPLACE THE 5 FT DEPTH MARKING. Correct By: 08-Mar-2019
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers of different kinds are stored on top of each other.
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
SEPARATE DIFFERENT CHEMICALS. DO NOT STORE DIFFERENT CHEMICALS ON TOP OF EACH OTHER. Correct By: 04-Mar-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) did not have emergency number post.
POST "DIAL "9-911" IN CASE OF EMERGENCY" OR SIMILAR BY THE EMERGENCY PHONE IN THE PHONE AREA. Correct By: 04-Mar-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-March-2019