[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not installed. Skimmer equalizer line not plugged at the pool wall.
Do not operate the pool when the outlet covers are not installed. PLUG THE SKIMMER EQUALIZER LINES AT THE POOL WALL. Correct By: 14-Jun-2023
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. One of the new skimmer weirs is stuck
All equipment must be maintained in accordance with the manufacturers specifications. MODIFY THE SKIMMER WEIR SO THAT IT FLOATS FREELY IN THE SKIMMER. Correct By: 14-Jun-2023
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR FLOW METER. Correct By: 14-Jun-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 07-June-2023

Comments
Keep documentation of the ASSE 1013 backflow preventer’s annual inspection available at the pool facility for review by the health department.

Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed 7/16/2019. The covers have a 7 year life span and must be replaced before 7/16/26.

The operator was observed performing onsite chemical tests appropriately