[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not compliant covers. The main drain covers have expired.
Do not operate the pool without compliant outlet covers. Install compliant outlet covers prior to placing the pool back into operation. REPLACE THE MAIN DRAIN COVERS RIGHT AWAY. KEEP A COPY OF THE CERTIFICATE OF COMPLIANCE FOR THE COVERS AT THE FACILITY Correct By: 02-Jul-2021
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not installed on skimmer equalizer outlets.
Do not operate the pool when the outlet covers are not installed. INSTALL VGB COMPLIANT COVERS OVER THE SKIMMER EQUALIZER OUTLETS OR PLUG THE OUTLET AT THE WALL. Correct By: 02-Jul-2021
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely. PROVIDE AIR GAP FOR FILTER BACKWASH LINE. Correct By: 02-Jul-2021
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing.
Repair gates or doors in order to be self-closing and lockable. ADJUST THE SPRING ON THE GATE SO THAT IT SELF-CLOSES. Correct By: 02-Jul-2021
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage areas were not secured.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas. KEEP EQUIPMENT ROOM LOCKED. Correct By: 30-Jun-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 30-June-2021

Comments
The operator was observed performing onsite chemical tests appropriately
Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed 7/1/2014. The covers have a 7 year life span and must be replaced before 7/1/2021.

When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm