3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The date of installation of the main drain covers is unknown.
THE EXISTING DRAIN COVERS HAVE A LIFE SPAN OF 5 YR. IF THE DRAIN COVERS ARE OLDER THAN 5 YRS OR IF THE DATE OF INSTALLATION OF THE DRAIN COVERS IS UNKNOWN REPLACE THE DRAIN COVERS. RETAIN THE CERT OF COMPLIANCE, INSTALL INSTRUCTIONS, AND THE CERT OF INSTALL Correct By: 15-May-2019
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Repeat Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR THE FLOW SWITCH SO THAT THE UNIT STOPS PUMPING CHEMICALS WHEN THE FLOW IS STOPPED.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Water leaks so the skimmers do not function properly.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE WATER LEAKS AND MAINTAIN THE PROPER WATER LEVEL SO THE SKIMMERS WORK PROPERLY. Correct By: 15-May-2019
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 388 GPM BUT NO MORE THAN 420 GPM Correct By: 01-Aug-2018
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
REPAINT THE 3 "ZERO DEPTH" MARKINGS AT THE END OF THE POOL. LETTERING MUST BE AT LEAST 4 INCHES IN HEIGHT AND NO MORE THAN 24 INCHES AWAY FROM THE WATER SURFACE. Correct By: 01-Aug-2018
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Repeat Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
REMOVE THE BAG OF SODA ASH FROM THE FLOOR OF THE PUMP ROOM. Correct By: 01-Aug-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not tested monthly and recorded.
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FLOW SWITCH MONTHLY. Correct By: 01-Aug-2018
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 24-July-2018
Comments |
---|
Corrections that have been made since the last inspection dated 6-5-18 -Alkalinity is tested and recorded weekly -ASSE 1013 backflow preventer has been inspected -the flow meter is working -a test kit is available for testing |