3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat The disinfection feeder was replaced with one with a different capacity.
SUBMIT AN ERN TO ODH FOR THE REPLACEMENT OF THE DISINFECTION FEEDER.
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL A VACUUM GAUGE AND PRESSURE GAUGE FOR THE SPA JET PUMP AND USE TO DETERMINE THE FLOW RATE. POST THE PUMP CURVE AND THE CALCULATIONS FOR DETERMINING THE TDH
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
INCREASE pH
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm
INCREASE ALKALINITY.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 21-August-2019
Comments |
---|
RECORD ACC FUNCTION TEST ON THE WEEKLY OPERATIONAL SHEET 4(B)(i) A means of determining rate-of-flow shall be properly installed, provided and maintained on all water pumps so that the rate of circulation can be accurately determined. 5.1(F)(2) Flow measuring devices. A means of determining rate-of-flow shall be properly installed and maintained on all public swimming pools, special features and jet pumps so that the rate of flow can be accurately determined and easily observed. One of the following methods to measure flow shall be used: (a) A flow meter; or (b) A pump curve specific for the pump and impellor. The pump curve shall be conspicuously posted in the filter room and shall be marked up to display the formula or means for calculating the gauge readings into the total dynamic head (TDH) and the flow in gallons per minute (gpm). A functional compound gauge shall be installed on the suction side of the pump, at or near the hair and lint strainer. A functional pressure gauge shall be installed on the pressure side of a pump, at or near the impellor housing; |