[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The flow rate exceeds max filter flow.
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE FLOW TO BETWEEN 51 AND 74 GPM. Correct By: 01-Aug-2020
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate does not self-close.
REPAIR GATE SO THAT IT SELF-CLOSES AND LATCHES. Correct By: 01-Aug-2020
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly. PARTIALLY DRAIN POOL TO LOWER CYA LEVEL Correct By: 01-Aug-2020


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 29-July-2020

Comments
CHECK SCREWS IN THE MAIN DRAIN COVER. ALL 4 SCREWS SHOULD BE IN PLACE.

Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals.

Corrections made since the last inspection
-bathroom has been repaired
-hand rail is tight
-pH level within range
-SVRS was tested and recorded.