[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. -Observed flow rate at 48gpm. Minimum flow rate for 29500 gallon pool at a 480gpm turnover rate should be 61gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. -Adjust flow rate to the determined gpm recommended by Ohio Department of Health.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 19-August-2022