3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
APPROVAL FROM ODH FOR THE CHEMICAL FEEDER REPLACEMENT HAS NOT BEEN RECEIVED YET.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
RECORD TEMP DAILY
Correct By: 11-Aug-2021
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gates or doors were not self-closing and lockable.
Repair gates or doors in order to be self-closing and lockable.
INSTALL SELF-CLOSING AND LATCHING GATE THAT MEETS ALL OTHER REQUIREMENTS. CONTACT ODH FOR PLAN REVIEW REQUIREMENTS.
3701-31-04 (B)(6)(z) / Special features are maintained in good repair and according to manufacturer specifications.
Repeat Special features were not maintained in good repair or in accordance with the manufacturer specifications.
Repair/maintain all the special features in good repair and in accordance with the manufacturer's specifications. If necessary, replace broken components.
SLIDE SCREWS AND BOLTS ARE LOOSE. REPORTEDLY, A NEW SLIDE WILL BE INSTALLED.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 06-August-2021