3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH). Pump replaced.
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT OF THE PUMP. StaRite PE5D-181L replaced with Pentair Intelliflo veritable speed.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat SVRS and ACC test results were not maintained.
The test results for these devices must be kept on site for review.
TEST AND RECORD RESULTS FOR THE ACC AND THE SVRS ON THE WEEKLY LOG SHEET.
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Repeat Chemicals not stored properly.
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
-MOVE ALKALINITY UP CONTAINER FROM UNDER THE LIQUID CHEMICALS.
-REMOVE THE WOOD STAIN AND PAINT FROM THE PUMP ROOM.
-STORE THE BAGS OF SHOCK OFF OF THE FLOOR.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 20-April-2022
Comments |
---|
The Certificate of Compliance for the main drain cover is available in the equipment room. Our records show that the main drain suction outlet covers (AquaStar WAV12) were installed on 10/26/2018. The covers have a 5 year life span and must be replaced before 10/26/2023. THE SPA JET TIMER WAS NOT AUTOMATICALLY TURNING OFF. |