3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The valve to the probe cell and flow switch is not working.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE VALVE TO THE FLOW SWITCH / PROBE CELL. REPEAT VIOLATION Correct By: 20-Nov-2020
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 54 GPM. REPEAT VIOLATION Correct By: 20-Nov-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 13-November-2020
Comments |
---|
BECAUSE THE 2 LISTED VIOLATIONS ARE REPEAT VIOLATIONS CALL ME WHEN THEY ARE CORRECTED. 440-219-7158 |