[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool. SUBMIT AN ERN FOR THE REPLACEMENT OF THE CIRCULATION PUMP.
3701-31-04 (C)(7) / Spa water temperature is less than 104 degrees Fahrenheit/ thermometer is provided
Spa water temperature was greater than 104 degrees Fahrenheit.
Do not operate the spa at a water temperature greater than 104 degrees Fahrenheit. Reduce the water temperature to 104 degrees or less. REDUCE WATER TEMPERATURE IN THE SPA BY AT LEAST 1 DEGREE TO 104 DEGREES OR BELOW. Correct By: 08-Apr-2024


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 05-April-2024

Comments
Equipment requiring ODH plan approval has been replaced since the inventory report dated 3-23-21 without submitting an ERN to ODH. The circulation pump Sta-Rite PE5D-181L .75 HP was replaced with a Pentair Intelliflo VSF.