3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Weirs were missing in the skimmer boxes.
All equipment must be maintained in accordance with the manufacturers specifications.
INSTALL MISSING WEIRS IN ALL THE SKIMMER BOXES. Correct By: 03-May-2018
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. The minimum required flow rate is 393 gpm and the reading was 375 gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW TO AT LEAST 393 GPM. Correct By: 04-Apr-2018
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly. Some of the reagents are either more than a year old or not date marked.
Obtain fresh reagents and store them properly.
DISCARD THE REAGENTS THAT ARE DATED MORE THAN ONE YEAR OLD OR NOT DATE MARKED AT ALL. Correct By: 04-Apr-2018
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool.
Provide the non-telescopic reach pole and personal floatation device at the pool at all times.
OBTAIN / PROVIDE / LOCATE IN PLAIN SIGHT A RING BUOY WITH A 30-60 FT LENGTH ROPE. Correct By: 03-May-2018
3701-31-04 (E)(4)(e)(vii) / Lifeguards have a CPR pocket mask and rescue tube on their person
Lifeguards did not have a CPR pocket mask on their person.
Provide lifeguards with CPR pocket masks and rescue tubes and require that these items be with the lifeguard at all times while on duty.
LIFEGUARD MUST KEEP A CPR MASK ON HIM WHEN ON DUTY. Correct By: 04-Apr-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 03-April-2018
Comments |
---|
CHECK THE CHLORINE LEVELS ON YOUR RECORD SHEETS. TOTAL CHLORINE IS THE SUM OF THE FREE AND COMBINE CHLORINE. COMBINE CHLORINE MUST BE 1. PPM OR LESS. |