3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Many skimmer weirs were missing
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING SKIMMER WEIRS. Correct By: 17-Jun-2019
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present
Remove all cross connection hazards from the pool area.
PROVIDE AN AIR GAP ON THE FILL SPOUT. YOU CAN SHORTEN THE FILL SPOUT SO THAT IT IS ABOVE THE RIM OF THE STAND PIPE. Correct By: 17-Jun-2019
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPLACE THE PRESSURE GAUGE ON ONE OF THE FILTERS. Correct By: 17-Jun-2019
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical chlorine pucks were stores in a basket by the filter..
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
STORE CHEMICAL PUCKS IN A CLOSED CONTAINER. Correct By: 13-Jun-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 12-June-2019
Comments |
---|
Our records show: The main drain suction outlet cover (AquaStar WAV 12) was installed 8/11/2014. The cover has a 5 year life span and must be replaced before 8/11/2019. |