3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. It appears that the flow control valve does not work.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE FLOW CONTROL VALVE SO YOU CAN REDUCE THE FLOW RATE. Correct By: 14-Jan-2024
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The flow rate exceeds that maximum allowable flow of the filters.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW RATE TO 63 GPM OR LESS, OR REPLACE THE FILTER WITH ONE THAT HAS A HIGHER FLOW RATING. Correct By: 14-Jan-2024
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Repeat Corrected During Inspection Chemical containers were stored without labels identifying the contents. pH adjust chemical was stored on top of the chlorine.
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
DO NOT STACK DIFFERENT TYPES ON CHEMICAL ON TOP OF EACH OTHER. Correct By: 14-Dec-2023
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not tested monthly
Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH FUNCTION MONTHLY. RECORD IT ON YOUR LOG SHEET. Correct By: 16-Dec-2023
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The test kit provided was not adequate to test for all the water quality parameters required to be regularly monitored. pH and chlorine reagents not available.
Obtain a test kit that can properly measure all the required water quality parameters.
OBTAIN DPD CHLORINE REAGENTS FOR TESTING FREE, COMBINE, AND TOTAL CHLORINE AND FOR pH. Correct By: 16-Dec-2023
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not answered at the front deck..
Ensure that the emergency device is functioning properly.
THE EMERGENCY PHONE MUST BE ANSWERED AT THE FRONT DECK IMMEDIATELY OR THE POOL PHONE MUST RING DIRECTLY TO THE EMERGENCY SYSTEM - 9-1-1. Correct By: 16-Dec-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-December-2023
Comments |
---|
DOUBLE CHECK THE TESTING OF THE ALKALINITY. MY TESTING SHOWED LESS THAN WHAT WAS RECORDED ON THE RECORD SHEET. |