[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical The ACC is not functioning properly.
REPAIR THE ACC SO THAT IS DISPLAYS CHEMICAL LEVELS ACCURATELY AND ADJUSTS CHEMICALS TO ACCEPTABLE LEVELS. Correct By: 20-Aug-2017
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. Records were not available during the inspection.
All facility records must be maintained and available for review upon request. KEEP RECORDS AT THE FACILITY. RECORDS MUST BE ACCURATE AND COMPLETE. Correct By: 20-Aug-2017
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The automatic chemical controller is not operating properly. It continues to add/make chlorine even though the level is more than 20 ppm. The displace shows less than 1 ppm.
All equipment must be maintained in accordance with the manufacturers specifications. HAVE THE AUTOMATIC CHEMICAL CONTROLLER REPAIRED OR REPLACED. Correct By: 20-Aug-2017
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 08-Jun-2017
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 08-Jun-2017
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. The reach pole is 15 ft.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times. SHORTEN THE REACH POLE TO 12 FT. Correct By: 20-Aug-2017


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 18-August-2017

Comments
PROVIDE A SIGN THAT STATED "WARNING POOL CLOSED" WHEN THE POOL IS CLOSED.

THE INFORMATION SUPPLIED ON THE MAIN DRAIN COVERS IS NOT ACCURATE. SUPPLY ACCURATE RECORDS ON THE DRAIN COVERS.