3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The equalizer lines are not covered with VGB compliant covers.
INSTALL VGB COMPLIANT COVERS OVER THE EQUALIZER LINES UNDER THE SKIMMERS OR PLUG THE EQUALIZER LINES AT THE POOL WALL. EQUALIZER LINES ARE SUCTION OUTLETS. Correct By: 05-Aug-2017
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
TEST THE FUNCTIONING OF THE SVRS MONTHLY AND RECORD ON THE WEEKLY RECORD SHEET. Correct By: 05-Aug-2017
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The skimmers are missing the weirs that provide proper skimming.
All equipment must be maintained in accordance with the manufacturers specifications.
INSTALL WEIRS (FLAPPERS) IN THE SKIMMER BOXES SO SKIMMING IS MORE EFFECTIVE. Correct By: 05-Aug-2017
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge.
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON THE FILTER BACKWASH LINE. Correct By: 05-Aug-2017
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. The flow rate was 110 gpm and the minimum flow rate is 117 gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 117 GPM IF POSSIBLE. Correct By: 05-Aug-2017
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH UP TO 7.2 AND BELOW 7.8. Correct By: 05-Aug-2017
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. The pole was only 9 ft long.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
PROVIDE A POLE WITH THE SHEPHERD'S CROOK THAT IS 12 FT LONG. Correct By: 15-Jul-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 07-July-2017