3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 18-Jul-2022
3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
THE FENCE HAS NOT BEEN APPROVED YET. REPORTEDLY, ODH HAS BEEN CONTACTED ABOUT THE PROJECT.
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Repeat Backflow prevention devices were not maintained to function properly. An ASSE 1015 backflow preventer has been installed. This is the incorrect application for a 1015.
Have the backflow prevention device replaced so that backflow is prevented.
INSTALL AN ASSE 1013 ON THE WATER FILL LINE.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 76 GPM.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. The depth markings are more than 25 ft apart in the southeast corner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
ADD ONE DEPTH MARKING IN THE SOUTHEAST CORNER.
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
(REPEAT) A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool.
Provide a proper floatation device at all times.
PLACE RING BUOY WITH ROPE IN POOL AREA.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 11-July-2022