3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. Faucet by gate not backflow protected.
Remove all cross connection hazards from the pool area.
INSTALL A 1011 BACKFLOW PREVENTER ON THE HOSE BIB BY THE GATE. Correct By: 07-Jun-2022
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 69 GPM BUT LESS THAN 120 GPM. Correct By: 07-Jun-2022
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps. Waterfall pump.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL A PRESSURE AND VACUUM GAUGE ON THE WATERFALL PUMP. Correct By: 07-Jun-2022
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not tested monthly.
Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC FLOW SWITCH/PUMP INTERLOCK MONTHLY. Correct By: 01-Jun-2022
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
PLACE FIRST AID KIT WHERE SWIMMERS CAN ACCESS IT. Correct By: 01-Jun-2022
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not available.
REINSTALL THE EMERGENCY PHONE.. Correct By: 01-Jun-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-May-2022
Comments |
---|
Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. The Certificate of Compliance for the main drain cover(s) is/are available in the equipment room. Our records show that the main drain suction outlet covers (AquaStar 8MF) were installed 7-27-2018. The covers have a 5 year life span and must be replaced before 7-27-2023. The waterfall pump outlets covers (AquaStar WAV 12) were installed 7-27-2018. The cover have a 5 year life span and must be replaced before 7-27-2023. |