3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level was below 1 ppm.
This is a critical operational items and poses an imminent health hazard.
THE WADING POOL MUST CLOSE UNTIL THE FREE CHLORINE LEVEL IS 1 PPM OR MORE. PLEASE NOTIFY THE HEALTH DEPARTMENT WHEN THE VIOLATION HAS BEEN CORRECTED. 440-219-7158
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
TEST CYA WEEKLY Correct By: 18-Jul-2019
3701-31-04 (B)(6)(e) / Equipment identification labels are maintained or on file
Equipment identification labels were not maintained and/or not on file. FLow rate was 11 gpm
Replace the missing equipment labels or have the proper equipment information on site for each piece of equipment.
MAINTAIN FLOW RATE BETWEEN 12.5 AND 18 GPM. Correct By: 18-Jul-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY Correct By: 18-Jul-2019
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 16-July-2019