[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. INCREASE ORP TO AT LEAST 650 MV
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE THE FLOW TO 76 GPM BUT LESS THAN 98 GPM.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate does not consistently self-close.
TIGHTEN THE SPRING ON THE GATE SO THAT IT CONSISTENTLY SELF-CLOSES. Correct By: 23-Aug-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 16-August-2018