3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Skimmer is missing weir.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING WEIR IN THE SKIMMER
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
SHORTEN PIPE FROM FILTER TO 12" ABOVE THE RIM OF WALL AROUND DRAIN
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL A PRESSURE AND VACUUM GAUGE BEFORE AND AFTER THE JET PUMP OR INSTALL A FLOW METER WITH THE ADDITIONAL LENGTH OF FOR THE SPA JET PUMP.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 27-August-2019