3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Three of the four skimmer boxes are missing the weirs.
All equipment must be maintained in accordance with the manufacturers specifications.
INSTALL WEIRS IN THE SKIMMERS.
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
THE END OF THE PIPE FROM THE FILTERS MUST BE ABOVE THE LEVEL OF THE FLOOR DRAIN BY AT LEAST 2 INCHES
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER Correct By: 21-Aug-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate was not self-closing.
WORK ON THE GATE AGAIN TO MAKE IT SELF-CLOSING Correct By: 21-Aug-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 13-August-2019
Comments |
---|
When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm |