3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 30-Jul-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 30-Jul-2018
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 30-Jul-2018
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 27-July-2018
Comments |
---|
Corrections that have been made since the last inspection dated 6-18-18 -the weirs are in the skimmer -the ACC and SVRS and tested and recorded |