3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
TEST AND RECORD FREE, COMBINE, AND TOTAL CHLORINE, AND pH EVERY 4 HRS, TEMPERATURE DAILY, ALKALINITY AND CYANURIC ACID WEEKLY, AND SVRS MONTHLY Correct By: 09-Aug-2018
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW RATE TO 63 GPM OR LESS. Correct By: 09-Aug-2018
3701-31-04 (B)(6)(b) / Replacement pipe is rigid PVC or the equivalent
Repeat Replacement pipe was not rigid PVC or equivalent.
Replace the non rigid PVC pipe with the proper rigid PVC pipe for public swimming pools.
REPLACE THE RUBBER COUPLINGS WITH RIDGED PIPE.
3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Repeat Throttle valve was not properly maintained/adjusted.
Throttle valves must be maintained in the same position was when originally installed and approved. Restore the setting of the throttle valve and lock it into place.
PLACE THE MAX FLOW (63 PGM) AND MIN FLOW (38 GPM) BY THE FLOW METER
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN LADDER.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Repeat Not all testing reagents are available. OTO is used.
OBTAIN AND USE A DPD TEST KIT FOR FREE, COMBINE AND TOTAL CHLORINE, pH, ALKALINITY, CYANURIC ACID, AND WATER TEMPERATURE
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 09-August-2018