[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage areas were not secured. -Observed the main door in the hallway to the equipment room was not locked. Tenants have laundry facilities and apartments on this floor. A sign was posted that it was for employees only, but the door is not secured. -The equipment room is a shared space with dumpsters and water heaters and other equipment, and the operator noted that the fire department does not allow the door to be locked. -Discussed creating a cage around the equipment and chemcials.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas.
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly. -Observed expired reagents in the test kit. REPLACE ANY EXPIRED REAGENTS.
Obtain fresh reagents and store them properly.
3701-31-04 (E)(2)(d) / First aid kit provided
Corrected During Inspection First aid equipment was not provided. -Observed there was no first aid kit available at the pool. -The operator obtained the test kit and brought it out to the pool.
Provide first aid equipment, including a first aid kit, at the pool at all times.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 07-July-2023

Comments
Our records show that the main drain suction outlet covers (A & A Channel )were installed 10/18/13. The covers have a 10 year life span and must be replaced before 10/18/2023.

Discussed the requirements for test kits. Test strips are not to be used, because they are not a "DPD" test. Per OAC 3701-31-04-(D)(8):
(a) The disinfection tests shall measure the free chlorine residual, the total or the combined chlorine residual or the bromine residual of a public swimming pool, with a test that uses diethyl l-p-phenylenediamine (DPD).
(b) If water quality results cannot be obtained by a standard DPD test kit, the licensor may require the more specific FAS-DPD test.
(c) Test kit reagents shall be fresh, properly stored to prevent degradation and used in accordance with the manufacturer's specifications.