3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
REWORK PIPE FROM FILTER TO DRAIN TO PROVIDE AN AIR GAP. CURRENTLY IT HAS AN AIR BREAK
3701-31-04 (B)(6)(cc)(i) / Starting blocks and diving platforms shall be maintained in good repair.
Repeat Starting blocks were in disrepair.
Repair, restore or replace the starting blocks to good repair.
REPLACE MISSING SCREWS IN THE STARTING BLOCKS
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
REPLACE THE MISSING TREAD ON THE LADDER STEPS
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The gate door was left open.
There are gaps under the fence and gate greater than 4 inches.
KEEP THE GATE CLOSED.
ELIMINATE GAPS UNDER THE FENCE AND GATE THAT ARE GREATER THAN 4 INCHES.
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Repeat Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
ATTACH THE CHEMICAL FEEDER PUMPS TO THE WALL OR SHELF TO ELIMINATE A CHEMICAL HAZARD
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Repeat Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area.
Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area.
POST A SIGN THAT STATE THE LOCATION OF THE EMERGENCY PHONE.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 15-July-2019
Comments |
---|
Corrections made since the 6-27-19 inspection -main drain cover COC available in pump room. Covers are current -flow rate is above 316 gpm (currently at 330 gpm) -alkalinity is at acceptable level of 60 ppm or above (70 ppm currently) -ACC flow switch is working -ACC flow switch is tested and recorded |