3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat The pump was replaced with approval form the Ohio Dept of Health.
SUBMIT AN ERN TO ODH FOR THE REPLACEMENT OF THE PUMP
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR/REPLACE THE FLOW METER. ENSURE THAT THE INSTALLATION IS ACCORDING TO THE MANUFACTURERS INSTRUCTIONS
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
REPAINT THE NO DIVING SIGNS NO MORE THAN 25 FT APART AND NO MORE THAN 24 INCHES FROM THE EDGE OF THE WATER.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
3701-31-04 (E)(2)(c) / Safety lines provided
Safety line to mark the change in depth of the pool was not attached to the inside wall of the pool.
ATTACH THE SAFETY LINE TO THE INSIDE WALL OF THE POOL.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-August-2018