3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The main drain covers are not VGB compliant.
REPLACE THE MAIN DRAIN COVERS WITH COMPLIANT COVERS. RETAIN THE COC, INSTALL INSTRUCTIONS, AND THE COI
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. the flow rate exceeds the max allowable flow for the filters
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW TO 63 GPM OR LESS.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-July-2018
Comments |
---|
Max and Min flow rate is written on pipe by flow meter CHECK THE FLOW METER FOR DIRT INSIDE WHICH MAY BE EFFECTING THE ACCURACY OF THE READING. |