3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 23-August-2017