3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The flow rate exceeds the flow rating of the drain covers
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW RATE SO AS NOT TO EXCEED THE FLOW RATE OF THE DRAIN COVERS (125 GPM) OR REPLACE THE DRAIN COVERS WITH ONES WITH A HIGHER FLOW RATE.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 16-July-2019
Comments |
---|
Corrections made since the 6-7-19 inspection -An air gap is on the filter backwash discharge line -the hand rail seems to the as tight as possible -the gat self-closes -the chlorine tank is labeled - |