3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation CONTACT HEALTH DEPARTMENT WAS REPAIR/REPLACED TO REINSPECT PRIOR TO OPERATING THE POOL AND SPA.
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
3701-31-04 (B)(6)(u) / Ventilation system is maintained/ free of hazards
EXCESSIVE HUMIDITY. PAINT PEELING FROM WALLS AND CEILINGS
REPLACE REPAIR VENTILATION AND DEHUMIDIFIER/HUMIDIFIER
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool.
Provide a proper floatation device at all times ATTACH ROPE TO FLOTATION DEVICE.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-January-2020