3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Flow rate exceeds filter max allowable flow rate.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE FLOW RATE TO 51 TO 74 GPM.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The shut off valve on the automatic chemical controller test cell does not function properly.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE VALVE ON THE ACC TEST CELL.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present. No air gap on water fill line.
Remove all cross connection hazards from the pool area.
PROVIDE AN AIR GAP ON THE WATER FILL LINE.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Perimeter barrier had gaps greater than 4 inches.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
REPAIR FENCE WHERE HOLES AND GAPS ARE UNDER THE FENCE.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gates or doors were not self-closing and self-latching..
Repair gates or doors in order to be self-closing and latching.
REPAIR GATE SO THAT IT SELF-LATCHES.
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
REDUCE CYANURIC ACID. Correct By: 23-Aug-2022
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment not sanitary. Bandages are moldy and gloves are missing..
Provide first aid equipment, including a first aid kit, at the pool at all times.
REPLACE BANDAGES IN THE FIRST AID KIT AND SUPPLY DISPOSABLE GLOVES. Correct By: 23-Aug-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 16-August-2022
Comments |
---|
CDC DOES NOT RECOMMEND CHLORINE LEVEL EXCEED 10 PPM. |