[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. MODIFY THE WEIRS IN THE SKIMMER BOX SO THEY FLOAT FREELY WITH THE WATER LEVEL.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. Hose bib in equipment room not back flow protected.
Remove all cross connection hazards from the pool area. INSTALL A VACUUM BREAKER ON THE HOSE BIB IN THE EQUIPMENT ROOM. Correct By: 16-Aug-2022
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Repeat Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly. REDUCE CYA
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. REPAIR EMERGENCY PHONE. Correct By: 11-Aug-2022


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 09-August-2022

Comments
UNABLE TO DETERMINE IF THE FOUNTAIN FLOW METER IS FUNCTIONING. FOUNTAIN PUMP WAS NOT ON AT THE TIME OF INSPECTION. REPAIR FLOAT METER IF NECESSARY.