3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The skimmer equalizer lines were not covered with approved covers.
COVER THE EQUALIZER LINES WITH A VGB APPROVED COVER OR PLUG THE OUTLET AT THE WALL. Correct By: 26-Jun-2018
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
Backflow prevention devices were not maintained to function properly
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
HAVE THE BACK FLOW PREVENTER TESTED ANNUALLY. Correct By: 26-Jun-2018
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The perimeter fence should be with a self-closing door or gate. All ingress gates should be self-closing and self-latching.
KEEP THE INGRESS DOOR CLOSED. Correct By: 13-Jun-2018
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents. clarifier and algimyein were stored on top of chemicals tank. potassium peroxymonosulfate stored on top of unlabeled tank.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
KEEP CHEMICALS OFF OF THE TOP OF THE CHEMICALS TANKS. KEEP DIFFERENT CHEMICALS SEPARATE. Correct By: 13-Jun-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC FUNCTION MONTHLY. Correct By: 13-Jun-2018
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool.
Provide a proper floatation device at all times. Correct By: 26-Jun-2018
3701-31-04 (E)(3)(d) / "WARNING or DANGER - POOL CLOSED" sign(s) posted-when the pool is closed
The pool was closed but the "WARNING or DANGER - POOL CLOSED" sign(s) were not posted.
Post the "WARNING or DANGER - POOL CLOSED" sign at all times the pool is not available for use. Correct By: 26-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 12-June-2018
Comments |
---|
RETAIN THE CERTIFICATE OF COMPLIANCE FROM THE MAIN DRAIN COVERS. MAKE AVAILABLE THE DATE OF INSTALLATION. |