3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not installed.
Do not operate the pool when the outlet covers are not installed.
PLUG THE EQUALIZER OUTLET FROM THE SKIMMER ON THE INSIDE OF THE SKIMMER. Correct By: 15-Jun-2021
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-June-2021
Comments |
---|
The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions. The Certificate of Compliance for the main drain cover is available in the equipment room. Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed 5/1/2016. The covers have a 7 year life span and must be replaced before 5/1/2023. This drain cover has a maximum flow rating of 356 gpm. When replacing the covers, ensure that the new covers' flow rating will not be exceeded. 408 gpm Safety Data Sheets (MSDS) are kept in the equipment room and Personal Protective Equipment (PPE), chemical gloves and goggles, are available for handling chemicals. |