3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THIS VIOLATION IS A CRITICAL OPERATION ITEM AND POSES AN IMMINENT HEALTH HAZARD. CLOSE POOL UNTIL FREE CHLORINE LEVEL IS 1 PPM OR MORE AND THE HEALTH DEPARTMENT VERIFIES THAT THE FREE CHLORINE LEVEL IS 1 PPM OR MORE. CALL ME FOR A REINSPECTION AT 440-219-7158.
FRONT OFFICE MANAGER CLOSED THE POOL. Correct By: 26-Apr-2021
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
RECORD ALKALINITY WEEKLY. Correct By: 28-Apr-2021
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation. Flow meter is not working
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER. Correct By: 27-Apr-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH. Correct By: 28-Apr-2021
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 24-May-2021