3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The skimmer equalizer suction outlet are not covered with a compliant cover.
PLUG THE SKIMMER EQUALIZER LINE AT THE POOL WALL OR INSTALL VGB COMPLIANT COVERS. Correct By: 03-Aug-2017
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat The flow meter is not located properly.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL THE FLOW METER ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS WHICH USUALLY IS 10 TIMES THE DIAMETER OF THE PIPE DOWNSTREAM FROM THE ELBOW OR OTHER TURBULENCE AND AT LEAST 5 TIMES THE DIAMETER OF THE PIPE UPSTREAM FROM TURBULENCE. Correct By: 27-Sep-2017
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner and no more than 25 ft apart..
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
PLACE ADDITIONAL NO DIVING MARKINGS ON THE DECK SO THEY ARE NO MORE THAN 25 FT APART.
Correct By: 03-Aug-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 13-July-2017