3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
The disinfection chemical feeder pump Stenner 45M2 was replaced with a Stenner 45M5 without ODH approval.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT OF THE CHEMICAL FEEDER PUMP. Correct By: 08-Jul-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
INSTALL THE WEIR IN THE SKIMMER. Correct By: 15-Jul-2019
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON THE FILTER BACKWASH LINE. Correct By: 03-Jul-2019
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER Correct By: 03-Jul-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The wading pool gate does not self-close and latch.
ADJUST THE WADING POOL GATE SO THAT IT SELF-CLOSES AND LATCHES Correct By: 03-Jul-2019
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
INCREASE pH TO AT LEAST 7.2. Correct By: 03-Jul-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY TO AT LEAST 60 PPM Correct By: 03-Jul-2019
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
REPAIR THE EMERGENCY PHONE. Correct By: 03-Jul-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-July-2019
Comments |
---|
Our records have been updated to show: The main drain suction outlet cover (Waterway 640-472xV) was installed on 6-1-19. The cover has a 7 year life span and must be replaced before 6-1-26. |