3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Chlorine disinfectant residual was less than 2 ppm for the spa
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 2 ppm or above prior to placing the spa back into operation.
THIS VIOLATION WAS CORRECTED AT THE TIME OF INSPECTION BY ADJUSTING THE ORP SET POINT. FREE CHLORINE WAS 5.4 AFTER 20 MINUTES. Correct By: 20-Oct-2021
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 100 GPM. Correct By: 27-Oct-2021
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 20-October-2021